Three-Phase Power
Convert between kW, kVA, kVAR, current and power factor for single- and three-phase systems. Enter the voltage and one value (power or current) and get every quantity, plus the recommended kVA to size a UPS or generator with margin. All in your browser.
All quantities
| Quantity | Value | Detail |
|---|
UPS / generator sizing
Rule of thumb: kVA = kW / PF / 0.8. Keep the UPS or
generator running at no more than 80 % to absorb
inrush peaks and future expansion.
How it is calculated · kW, kVA, kVAR and PF
1. Three-phase (V = line-to-line):
kVA = √3 · V · I / 1000 and I = kVA · 1000 / (√3 · V).
Single-phase: without the √3 → kVA = V · I / 1000.
2. The power factor relates apparent to
active power: kW = kVA · PF, where
PF = cosφ is between 0 and 1.
3. The power triangle:
kVA² = kW² + kVAR², so
kVAR = √(kVA² − kW²) (reactive power).
4. Sizing: start from active power and
leave margin → kVA = kW / PF / 0.8. The
0.8 reserves 20 % for inrush and growth.
Runs locally in your browser · no sign-up · nothing leaves your browser.
How it works
The calculator converts between all the electrical quantities of a single-phase or three-phase system from the voltage and one known value: power (kW or kVA) or line current, plus the power factor. For three-phase, with line-to-line V, it uses kVA = √3 · V · I / 1000 and I = kVA · 1000 / (√3 · V); for single-phase the same formulas without the √3. Powers are related by kW = kVA · PF and the power triangle kVA² = kW² + kVAR², which yields the reactive component: kVAR = √(kVA² − kW²).
It also sizes the UPS or generator with the practical rule kVA = kW / PF / 0.8: the 0.8 factor keeps the equipment loaded at 80 % of capacity at most, the reserve that good design practice (aligned with the NEC continuous-load criterion) sets aside for motor starting peaks and future growth. It includes presets for the common voltages: 220/230 V single-phase and 380/400/480 V three-phase.
Example: 10 kW motor on 380 V three-phase with 0.9 PF
- Apparent power:
kVA = 10 / 0.9 = 11.11 kVA. - Line current:
I = 11,111 / (√3 × 380) = 16.9 Aper phase. - Reactive:
kVAR = √(11.11² − 10²) ≈ 4.84 kVAR. - Recommended UPS or generator:
10 / 0.9 / 0.8 ≈ 13.9 kVA(a commercial 15 kVA unit).